Rotary Phase Converter Idler Sizing

The minimum rotary-phase-converter idler to make three-phase from single-phase: idler HP = max(start factor x largest single motor, total HP running at once). The idler must both start the largest motor across the line (a ~2x factor for normal loads, ~3x for a high-inertia or hard-starting load) and run the whole aggregate load. A 10 HP lathe with a 5 HP mill also running is max(2x10, 15) = 20 HP; a shop with a small 5 HP largest but 30 HP total running is governed by the 30 HP load. Undersized, the converter stalls or will not start the big motor; oversized, it wastes idle power. A rule-of-thumb screen; the converter manufacturer's data and the motors' locked-rotor current govern.

Run the calculator

Formula and source

start_demand_hp = start_factor x largest_motor_hp; idler_hp_min = max(start_demand_hp, total_running_hp); start_factor ~2 (normal) or ~3 (high-inertia).

Rotary phase converter idler-sizing rule of thumb (industry / converter-manufacturer guidance), by name; NEMA MG-1 across-the-line inrush behavior. The converter manufacturer governs.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.