Sanitary Drain DFU Sizing

Total drainage fixture units from a fixture list and the minimum pipe size for a horizontal branch, vertical stack.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: ICC.

Details, formula, and sources

ScopeTotal drainage fixture units from a fixture list and the minimum pipe size for a horizontal branch, vertical stack, or building drain. Per IPC 2027 §710 with Table 709.1 DFU values (unchanged from 2021 except the drinking fountain, now 0 DFU).

Formula or tabletotal DFU = sum(fixture count × DFU value). Minimum pipe size = smallest size whose table maximum ≥ total DFU: horizontal branch and stack per IPC Table 710.1(2); building drain per IPC Table 710.1(1) (slope-dependent).

Source and editionIPC 2027 (International Plumbing Code). Section 710; DFU values per IPC Table 709.1; capacities per Tables 710.1(1) and 710.1(2).

Free accessFree read-only access at codes.iccsafe.org.

What governsEstimate. AHJ and licensed plumber / gas fitter govern. Verify against the IPC / IFGC edition adopted in your jurisdiction.

API field namesfixtures, config, slope_in_per_ft, total_dfu, min_size_in