Septic Drainfield Capacity (Flow / Bedrooms)

The design flow and bedroom count a drainfield supports, from the trench length a lot can fit.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: North Carolina Department of Health and Human Services, Division of Public Health...

Details, formula, and sources

Scope300 ft of 3 ft trench at 0.6 gpd/ft^2 serves 540 gpd (3 bedrooms). AHJ governs.

Formula or tableDesign flow supported = available_trench_ft × trench_width_ft × application_rate_gpd_per_ft² (the inverse of the required-area sizing). Bedrooms = floor(design_flow / gpd_per_bedroom); EPA baseline 150 gpd/bedroom.

Source and editionU.S. EPA Onsite Wastewater Treatment Systems Manual (EPA/625/R-00/008) by name; per-state and per-county application rates and per-bedroom design flows set by local code (not bundled).

Free accessFree at epa.gov/septic. State application-rate and per-bedroom-flow tables free on each state department of health / DEQ site.

What governsEstimate. AHJ and licensed plumber / gas fitter govern. Verify against the IPC / IFGC edition adopted in your jurisdiction.

API field namesavailable_trench_ft, application_rate_gpd_per_ft2, trench_width_ft, gpd_per_bedroom, design_flow_gpd, absorption_area_ft2, bedrooms