Server Inlet Temperature and Humidity Envelope

Calculates dew point and classifies server inlet air against entered recommended and allowable temperature.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Relative-humidity, and dew-point limits. It exposes the hot-and-humid corner where dry bulb passes but dew point fails; the installed equipment class governs.

dew point is calculated from dry bulb and RH with the Tetens correlation, then dry bulb, RH, and dew point are checked independently against entered recommended and allowable limits.

ASHRAE TC 9.9 thermal guidelines for data-processing environments and the Tetens saturation-vapor-pressure approximation. The current equipment-class limits govern.

The dew-point correlation is public; envelope limits are entered rather than reproducing a proprietary table.

Estimate. AHJ and licensed professional govern.

Field names used by the API: dry_bulb_f, relative_humidity_pct, recommended_min_f, recommended_max_f, allowable_min_f, allowable_max_f, upper_dew_point_f, upper_rh_pct, alternative_temp_f, alternative_rh_pct, dew_point_f, dew_point_margin_f, warm_same_rh_dew_point_f, alternative_dew_point_f, alternative_dew_point_margin_f