Wood Shear Wall Unit Shear and Holdown (SDPWS / ASD)

The two numbers a wood shear wall is detailed for.

Run the calculator

Example

You enter

You get

No published worked example is on file for this calculation. It is checked against a hand-worked derivation of its method and an independent reference test.

Details, formula, and sources

ScopeThe unit shear v = V/b checked against the SDPWS nailing schedule, and the net holdown tension T = (V h - 0.6 W b/2)/b once the story shear tries to overturn the wall and only 0.6 times the tributary dead load resists it for wind, or (0.6 - 0.14 SDS) times it for seismic, where the vertical quake effect lightens the wall (the ASD combinations). An 8 ft wall taking 8 kip at 10 ft with 3,000 lb of dead load runs 1,000 plf and a 9.1 kip holdown; load the wall to 20,000 lb and gravity cuts the holdown to 4.0 kip, and past the balance point the holdown clamps to zero. Segmented wall; sill anchorage and chord bearing are separate. A design aid, not a substitute for the engineer of record's stamped lateral design.

Formula or tablev = V / b; Mot = V h; Mr = k W (b/2), k = 0.6 - 0.14 SDS (seismic; 0.6 for wind, SDS = 0); T = max((Mot - Mr) / b, 0).

Source and editionThe AWC SDPWS segmented shear-wall model with the ASCE 7 / IBC allowable-stress overturning check ((0.6 - 0.14 SDS)D seismic, 0.6D wind), as compiled in the AWC/APA wood-frame shear-wall design guides, by name.

Free accessAWC SDPWS is viewable free of charge through AWC's online reader; the unit-shear and overturning-couple arithmetic is public.

What governsEstimate. AHJ and licensed professional govern.

API field namesv_lb, b_ft, h_ft, w_lb, v_plf, mot_ftlb, mr_ftlb, t_lb