Air Mover Placement

How many air movers a water loss needs, low and high, from the IICRC worksheet.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: IICRC Airmover and Gallons Calculation Worksheet (US imperial, rev. 7.1.22).

Details, formula, and sources

ScopeOne per room, per 50-70 ft² of wet floor, per 100-150 ft² of wet wall and ceiling, and per inset.

Formula or tablelow = rooms + ceil(wet_floor_ft2 / 70) + ceil(wet_wall_ceiling_ft2 / 150) + insets; high = rooms + ceil(wet_floor_ft2 / 50) + ceil(wet_wall_ceiling_ft2 / 100) + insets. The wet-floor figure includes the lower walls to 2 ft. total_cfm = low count x 2,500 cfm nominal.

Source and editionIICRC Airmover and Gallons Calculation Worksheet, US imperial (rev. 7.1.22), which accompanies IICRC S500; S500 itself by name.

Free accessThe worksheet is free at iicrc.org; the S500 standard is licensed.

What governsEstimate. AHJ and licensed professional govern.

API field namesaffected_area_ft2, water_class, rooms, wall_ceiling_ft2, insets, air_mover_count, air_mover_count_high, total_cfm, cfm_per_ft2, placement_pattern