Negative Air Machine Sizing
Required CFM and unit count from room volume and target ACH.
Example
You enter
- Room volume (ft³) 8000
- Target air changes per hour 6
You get
- Required CFM 800
Details, formula, and sources
Required Negative Air Machine CFM = chamber_volume_ft³ × target_ACH / 60. 4-6 ACH for general containment; 12+ ACH for active mold remediation per IICRC S520-2024 §12.
IICRC S520-2024 §12 (Engineering Controls) by name; ASHRAE 170 (Ventilation of Health Care Facilities) by name for hospital-equivalent ACH.
IICRC / ASHRAE standards licensed; ACH principles free in published engineering texts.
Estimate. AHJ and licensed professional govern.
Field names used by the API: room_volume_ft3, target_ach, required_cfm
- Default target ACH 12 ACH (active remediation) unless user suppliesIICRC S520-2024 §12