Chilled-Water Thermal Ride-Through

Converts loop water volume and allowable temperature rise into stored sensible energy and minutes of IT-load...

Run the calculator

Example

You enter

You get

Details, formula, and sources

Converts loop water volume and allowable temperature rise into stored sensible energy and minutes of IT-load ride-through, then sizes the volume needed across generator transfer and chiller restart. Usable system volume and transient plant behavior govern.

stored Btu = gallons x 8.34 lb/gal x allowable delta-T; ride-through minutes = stored Btu/(IT kW x 3,412 Btu/hr) x 60.

The water sensible-heat storage relation with ASHRAE TC 9.9 guidance. Chiller restart sequence and usable system volume are manufacturer- and site-specific.

Mass x specific heat x temperature-rise energy storage.

Estimate. AHJ and licensed professional govern.

Field names used by the API: loop_volume_gal, it_load_kw, supply_temp_f, max_temp_f, generator_transfer_min, chiller_restart_min, smaller_loop_volume_gal, stored_cooling_btu, ride_through_min, ride_margin_min, smaller_loop_shortfall_min, required_volume_gal