Coil Bypass Factor and Apparatus Dew Point
Bypass factor BF = (t_lvg - t_adp)/(t_ent - t_adp), contact factor CF = 1 - BF, off the apparatus dew point (coil-surface temperature). 80 -> 55 F off a 50 F ADP -> BF 0.167, CF 0.833; a shallower coil bypasses more and dehumidifies worse. A design aid; the coil rating governs.
Formula and source
BF = (t_lvg - t_adp) / (t_ent - t_adp); CF = 1 - BF.
The coil bypass / contact factor and apparatus-dew-point definition from the ASHRAE Handbook - Fundamentals, by name.
Audience
This tile is built for hvac and the adjacent professions in the HVAC group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.
Related tools
Posture
Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.