Cooling Coil Total Load from Enthalpy Difference

The total heat a cooling coil removes, sensible plus latent.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: PDHonline (J. Primo).

Details, formula, and sources

ScopeQ = 4.5 x CFM x (h_ent - h_lvg) Btu/hr, the full sensible-plus-latent heat a coil removes, from the moist-air enthalpy drop. 2,000 CFM across a 31.48 -> 22.97 Btu/lb drop -> 76,590 Btu/hr (6.38 tons), well above the dry-bulb-only estimate. A design aid; the coil rating governs.

Formula or tableQ = 4.5 x CFM x (h_ent - h_lvg) Btu/hr; tons = Q / 12000.

Source and editionThe total-heat coil-load relation from the ASHRAE Handbook - Fundamentals, by name.

Free accessThe 4.5 x CFM x enthalpy-difference total-heat relation is a standard airside coil result. The coil rating governs.

What governsEstimate. AHJ and licensed professional govern.

API field namescfm, h_ent_btu, h_lvg_btu, q_btuh, tons