Cooling Coil Face Area for a Target Velocity

Required coil face area = CFM / target face velocity, the inverse of the face-velocity check.

Run the calculator

Example

You enter

You get

Details, formula, and sources

2000 CFM at the 500 fpm wet-coil limit needs 4.0 ft^2 (about 24x24 in). A larger face lowers velocity and carryover risk. The coil manufacturer's rated face velocity governs.

Required face_area_ft2 = CFM / target_face_velocity_fpm (the inverse of face_velocity = CFM / area); square side = sqrt(face_area x 144).

The cooling-coil face area from a target face velocity, standard coil-selection practice (ASHRAE), by name.

Face area = airflow / face velocity and the ~500 fpm wet-coil carryover limit are standard published coil-selection results.

Estimate. AHJ and licensed professional govern.

Field names used by the API: cfm, target_fpm, face_area_ft2, square_side_in