EGC Proportional Upsize for Increased Conductors (NEC 250.122(B))

When ungrounded conductors are increased in size for voltage drop or future capacity.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: IAEI Magazine (Keith Lofland); Mike Holt Enterprises.

Details, formula, and sources

ScopeThe equipment grounding conductor increases in the same circular-mil proportion per NEC 250.122(B). Base EGC and base phase area are user-supplied table values; the EGC need not exceed the ungrounded conductors. The AHJ governs.

Formula or tableratio = max(1, installed_phase_cmil / base_phase_cmil); upsized_EGC_cmil = base_EGC_cmil x ratio, then select the next standard AWG/kcmil at or above this. A ratio below 1 is clamped to 1 (the EGC is never reduced below its table size).

Source and editionNEC 2023 (NFPA 70). 250.122(B) (increase in size of equipment grounding conductors).

Free accessFree read-only access at nfpa.org/freeaccess.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesbase_egc_cmil, base_phase_cmil, installed_phase_cmil, ratio, upsized_egc_cmil