Parallel Conductor Ampacity

Total ampacity of paralleled conductor sets after the NEC fill and ambient adjustments.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NEC (NFPA 70) Article 310 parallel-conductor provisions + 310.15(C)(1) adjustment.

Details, formula, and sources

ScopeTotal ampacity of N paralleled conductor sets with the NEC more-than-three current-carrying-conductor and ambient adjustments, plus per-set load adequacy (1/0 AWG and larger only).

Formula or tableI_total = I_single x N x F_ccc x F_ambient, where N is the number of identical parallel sets, F_ccc is the more-than-three current-carrying-conductor adjustment (1.0 for <=3, 0.8 for 4-6, 0.7 for 7-9, 0.5 for 10-20, ...), and F_ambient the temperature correction. Per-set current I_set = I_load / N. Paralleling is permitted only at 1/0 AWG and larger.

Source and editionNEC (NFPA 70) Article 310 paralleled-conductor provisions and the 310.15(C)(1) adjustment factors, by name.

Free accessNFPA 70 free read-only at nfpa.org/freeaccess; conductor ampacities user-supplied from the adopted edition's ampacity table.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.