Egress Lighting Illuminance Compliance Check (NFPA 101 / IBC)

Egress illuminance against NFPA 101 / IBC.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Normal 1.0 fc avg / 0.1 fc min, emergency 90-min end 0.6 / 0.06, max/min <= 40:1. A 1.2/0.15/3.0 fc corridor is compliant; a 0.05 fc dark spot fails the emergency minimum even at a good average. The adopted code and AHJ govern.

normal: avg >= 1.0 fc, min >= 0.1 fc; emergency 90-min end: avg >= 0.6 fc, min >= 0.06 fc; max/min <= 40:1; pass = all.

The NFPA 101 Life Safety Code / IBC means-of-egress illumination requirements, by name.

The egress illumination minimums are in NFPA 101 and the IBC (NFPA publishes free-to-read access; many jurisdictions post the adopted IBC). The adopted edition and the AHJ govern.

Estimate. AHJ and licensed professional govern.

Field names used by the API: avg_fc, min_fc, max_fc, mode, max_min