Motor Branch-Circuit from Nameplate

Compute full-load current from HP / V / eta / PF; flag the design value as the larger of computed vs nameplate.

Run the calculator

Example

You enter

You get

Details, formula, and sources

125% branch-conductor + overload sizing.

Single-phase: I = HP * 746 / (V * eta * PF). Three-phase: I = HP * 746 / (sqrt(3) * V * eta * PF). Branch-circuit conductor at 125% per NEC §430.22; overload max at 115% or 125% per NEC §430.32 (SF >= 1.15 -> 125%).

NEC 2023 (NFPA 70). §430.6(A)(1) (reference-FLA tables), §430.22 (branch conductor 125% rule), §430.32 (overload sizing).

Free read-only access at nfpa.org/freeaccess.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: hp, voltage_V, phase, eta, power_factor, nameplate_fla_A, service_factor, computed_fla_A, design_fla_A, branch_conductor_125pct_A, overload_max_A