Motor Starting Voltage Dip

Voltage dip during motor start from locked-rotor current and conductor length.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: Ohm's-law voltage-drop method (first principles) + NEC Article 430 LRC.

Details, formula, and sources

ScopeWith terminal voltage and a pass/fail against the dip limit (contactor dropout risk).

Formula or tableV_drop = (2 for 1-phase, sqrt(3) for 3-phase) x LRC x L x (R cos phi + X sin phi), R = K / cmils per ft, X the conductor reactance and phi the locked-rotor power-factor angle (typ. pf 0.2-0.4); V_terminal = V_source - V_drop; %dip = V_drop / V_source x 100. K is the conductor constant (Cu ~12.9, Al ~21.2 ohm-cmil/ft) and LRC the motor locked-rotor current.

Source and editionImpedance voltage-drop method at the locked-rotor power factor (IEEE 141 by name); motor locked-rotor current per NEC Article 430 code-letter tables; contactor pickup/dropout ~85% nominal per NEMA ICS 2, by name.

Free accessNFPA 70 free read-only at nfpa.org/freeaccess; LRC user-supplied from the nameplate code letter or estimated as 6x FLA.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namessource_voltage_V, length_ft, cmils, lrc_A, phase, k_const, dip_limit_pct, v_drop_V, dip_pct, v_terminal_V