Noncoincident Loads: Larger of Heating vs A/C (NEC 220.60)

Applies NEC 220.60: where two loads (electric heat vs air-conditioning) are unlikely to run at the same time.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NEC 2023 (NFPA 70).

Details, formula, and sources

ScopeThe service calc carries only the larger and omits the smaller; the exception adds both where they operate simultaneously (a heat-pump compressor with supplemental strip heat). The AHJ judges noncoincidence.

Formula or tablecounted = both_can_run ? load_a + load_b : max(load_a, load_b); omitted = both_can_run ? 0 : min(load_a, load_b).

Source and editionNoncoincident loads, NEC 2023 220.60, with the simultaneous-operation exception, by name.

Free accessNEC is free to read at nfpa.org/freeaccess. Where two loads are unlikely to be in use at the same time, only the larger is counted; the exception adds both where they operate together (a heat-pump compressor with supplemental strip heat).

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesload_a_va, load_b_va, counted_va, omitted_va

Related tools