PDU Branch Loading and Failover Capacity
Applies the continuous-load allowance to a single- or three-phase PDU branch, converts usable current to kVA and kW.
Example
You enter
- Line voltage (V) 208
- Phase configuration three_phase
- Branch breaker rating (A) 30
- Continuous-load limit (%) 80
- Equipment power factor 0.99
- Measured draw per device (W) 450
You get
- Usable continuous current 24.0 A
- Branch capacity (kW) 8.55993
- Supported devices 19
- Survivor current at correct loading 24.0 A
- Pair filled survivor breaker (%) 159.814
Details, formula, and sources
Applies the continuous-load allowance to a single- or three-phase PDU branch, converts usable current to kVA and kW, and checks normal and paired-feed failover loading. The device nameplate, branch topology, and adopted electrical code govern.
usable current = breaker amperes x continuous-load fraction; kVA = V I for single phase or sqrt(3) V I for three phase; device count = floor(usable kW/device W).
NEC continuous-load sizing and the standard AC power relations. The adopted NEC edition, equipment ratings, and authority having jurisdiction govern.
Basic single- and three-phase power arithmetic; NEC continuous-load requirements are publicly summarized by authorities and manufacturers.
Estimate. AHJ and licensed professional govern.
Field names used by the API: line_voltage_v, phase_configuration, breaker_rating_a, continuous_load_pct, power_factor, device_draw_w, usable_current_a, branch_capacity_kw, supported_device_count, failover_current_a, pair_filled_survivor_breaker_pct
- Continuous fraction entered from the adopted electrical requirements, commonly 80% where 125% sizing appliesNEC / AHJ
- Balanced three phase equal phase loading and entered power factorplanning model