Rack Storage Flue Space and Beam Length

Checks the transverse gaps a bay actually provides, the beam length the nominal flue requires.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Checks the transverse gaps a bay actually provides, the beam length the nominal flue requires, and the longitudinal flue left after pallet overhang. A bay sized to fit its pallets gives 4 in where 6 in is nominal, and a deeper load closes the back-to-back flue to a third. NFPA 13 as adopted governs.

Required beam length = pallets x pallet width + transverse gaps x nominal flue; longitudinal flue = back-to-back spacing - 2 x overhang, with overhang = (load depth - frame depth) / 2.

NFPA 13 Standard for the Installation of Sprinkler Systems as adopted, with the commodity classification, storage height, and arrangement.

NFPA publishes its standards for free read-only online access; the nominal 6 in transverse and longitudinal flue is stated there.

Estimate. AHJ and licensed professional govern.

Field names used by the API: pallet_width_in, pallet_depth_in, pallets_per_bay, transverse_gaps, nominal_flue_in, beam_length_in, frame_depth_in, back_to_back_spacing_in, deeper_load_depth_in, transverse_gap_each_in, required_beam_length_in, beam_shortfall_in, pallet_overhang_in, longitudinal_flue_in, deeper_load_longitudinal_flue_in, deeper_load_flue_share_pct