Rack Storage Flue Space and Beam Length

Checks the transverse gaps a bay actually provides, the beam length the nominal flue requires.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: Apex Warehouse Systems.

Details, formula, and sources

ScopeChecks the transverse gaps a bay actually provides, the beam length the nominal flue requires, and the longitudinal flue left after pallet overhang. The end gaps are half-flues that pair with the next bay's at each upright, so two 48 in pallets need a 108 in beam, not 114; a deeper load closes the back-to-back flue to a third. NFPA 13 as adopted governs.

Formula or tableRequired beam length = pallets x pallet width + (transverse gaps - 1) x nominal flue, the two end gaps being half-flues that pair at the uprights (Apex: 6 in between loads, 3 in at each end); longitudinal flue = back-to-back spacing - 2 x overhang, with overhang = (load depth - frame depth) / 2.

Source and editionNFPA 13 Standard for the Installation of Sprinkler Systems as adopted, with the commodity classification, storage height, and arrangement.

Free accessNFPA publishes its standards for free read-only online access; the nominal 6 in transverse flue is stated there; a longitudinal flue is required in double-row racks over 25 ft.

What governsEstimate. AHJ and licensed professional govern.

API field namespallet_width_in, pallet_depth_in, pallets_per_bay, transverse_gaps, nominal_flue_in, beam_length_in, frame_depth_in, back_to_back_spacing_in, deeper_load_depth_in, transverse_gap_each_in, required_beam_length_in, beam_shortfall_in, pallet_overhang_in, longitudinal_flue_in, deeper_load_longitudinal_flue_in, deeper_load_flue_share_pct