Industrial Control Panel SCCR (UL 508A)

The short-circuit current rating of an industrial control panel by the UL 508A weakest-link method.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: UL 508A Supplement SB / NEC 409.110.

Details, formula, and sources

ScopeThe panel SCCR is the LOWEST of its power-circuit components' individual ratings (and the feeder OCPD interrupting rating), not the main breaker -- one 5 kA contactor caps the whole panel. Checked against the available fault per NEC 409.110. A current-limiting fuse can raise a weak component's combination rating.

Formula or tablepanel_sccr = min(component SCCRs, feeder OCPD interrupting rating); compliant when panel_sccr >= available_fault.

Source and editionThe UL 508A Supplement SB industrial-control-panel short-circuit current rating (weakest-link method), with NEC 409.110 / 110.10, by name.

Free accessThe weakest-link SCCR method is defined in UL 508A Supplement SB; NEC 409.110 is available through NFPA free online read-only access.

What governsEstimate. AHJ and licensed professional govern.

API field namescomponent_sccrs_ka, available_fault_ka, panel_sccr_ka