Service Load Calculation (NEC 220.82 Optional Method)

Optional-method dwelling demand (first 10 kVA at 100% + remainder at 40% + larger HVAC).

Run the calculator

Example

You enter

You get

Details, formula, and sources

Compared to the standard 220.42 method.

General load demand = first 10 kVA at 100% + remainder at 40%, where general load = 3 VA/ft^2 + 1500 VA per small-appliance and laundry circuit + nameplate of fixed appliances, range, dryer, water heater. HVAC larger of heating vs cooling added at 100% (220.82(C)).

NEC 2023 (NFPA 70). 220.82 (optional dwelling load calculation); 220.42 (standard method) for the comparison.

Free read-only access at nfpa.org/freeaccess.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: area_ft2, small_appliance_circuits, laundry_circuits, fixed_appliances_kw, range_kw, dryer_kw, water_heater_kw, hvac_heating_kw, hvac_cooling_kw, service_voltage, general_demand_va, optional_total_va, optional_demand_a