Service Load Calculation (NEC 220.82 Optional Method)

Optional-method dwelling demand (first 10 kVA at 100% + remainder at 40% + larger HVAC).

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NFPA; IAEI Magazine (International Association of Electrical Inspectors).

Details, formula, and sources

ScopeCompared to the standard Part III method (Table 220.45).

Formula or tableGeneral load demand = first 10 kVA at 100% + remainder at 40%, where general load = 3 VA/ft^2 + 1500 VA per small-appliance and laundry circuit + nameplate of fixed appliances, range, dryer, water heater. HVAC is the larger of cooling at 100% and heating at 100% (heat pump), 65% (central resistance or fewer than 4 separately controlled units) or 40% (4 or more separately controlled units) (220.82(C)).

Source and editionNEC 2023 (NFPA 70). 220.82 (optional dwelling load calculation); the Part III standard method (Table 220.45 lighting demand) for the comparison.

Free accessFree read-only access at nfpa.org/freeaccess.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesarea_ft2, small_appliance_circuits, laundry_circuits, fixed_appliances_kw, range_kw, dryer_kw, water_heater_kw, hvac_heating_kw, hvac_cooling_kw, service_voltage, general_demand_va, optional_total_va, optional_demand_a