Max Tributary Drainage Area for an Allowable Flow

The largest tributary catchment an inlet, pipe, or outlet rated for an allowable flow can accept.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: USEPA / NRCS.

Details, formula, and sources

ScopeA_acres = Q / (C x i). A 2-cfs outlet on asphalt (C 0.95) at 2 in/hr accepts up to ~45,850 ft^2 (1.05 ac); a rougher surface or lower intensity allows more. A design aid; the AHJ and the civil engineer govern.

Formula or tableA_acres = Q / (C × i); A_ft2 = A_acres × 43560. The Rational method Q = C × i × A solved for the area, C from bundled runoff coefficients per surface.

Source and editionRational method by name (public hydrology), solved for the area. C-values from public engineering practice.

Free accessRainfall intensity / IDF curves free at hdsc.nws.noaa.gov (NOAA Atlas 14).

What governsEstimate. AHJ and licensed plumber / gas fitter govern. Verify against the IPC / IFGC edition adopted in your jurisdiction.

API field namesallowable_flow_cfs, surface, rainfall_in_per_hr, max_area_acres, max_area_ft2