Sump / Ejector Basin Drawdown and Cycle Check

Drawdown volume, run and fill times, cycles per hour, and a short-cycle verdict for a sump or sewage-ejector basin against its inflow and pump rate.

Run the calculator

Formula and source

area_ft2 = (PI/4)(basin_dia/12)^2; drawdown_gal = area_ft2 x (drawdown_in/12) x 7.48; run_time_s = drawdown_gal / (pump_gpm - inflow_gpm) x 60; fill_time_s = drawdown_gal / inflow_gpm x 60; cycles_per_hr = 3600 / (run + fill); adequate = run_time_s >= min_run_s.

IPC 2021 Section 712 (Sumps and Ejectors) and the Hydraulic Institute pump-cycling guidance by name; first-principles basin geometry and cycle math.

Audience

This tile is built for plumbers and the adjacent professions in the Plumbing and Gas group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tiles

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.