Transformer Sizing

Required kVA from load and voltages.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: Alfa Transformer.

Details, formula, and sources

Formula or tablekVA = kW / power factor, rounded up to the next ANSI/IEEE C57 standard size; full-load current = kVA x 1000 / (√3 × V_LL) three-phase or kVA x 1000 / V single-phase, on each winding. Overcurrent protection (NEC 450.3) is not computed here.

Source and editionNEC 2023 (NFPA 70). Article 450 by name; the standard kVA steps per ANSI/IEEE C57. Overcurrent protection per Section 450.3, Table 450.3(B), is a separate step this tile does not compute.

Free accessFree read-only access at nfpa.org/freeaccess.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesload_kW, power_factor, primary_V, secondary_V, phase, required_kVA, next_standard_kVA