Cross-Connection Air Gap (IPC Table 608.16.1)

The minimum air gap for the most positive backflow protection there is.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: International Code Council (Louisiana LDH amended copy).

Details, formula, and sources

ScopeThe physical gap between a supply outlet and the flood-level rim, which nothing mechanical can defeat. IPC 2027 Table 608.16.1 (identical in 2021): 1, 1-1/2 or 2 in for effective openings up to 1/2, 3/4 or 1 in (1-1/2, 2-1/2 or 3 in near a wall), then twice the opening (three times within three diameters of a wall). A 1 in opening needs a 2 in gap (3 in near a wall); a 3/4 in opening near a wall needs 2-1/2 in, not 3 x 0.75. Checks a measured installed gap against the requirement. For indirect-waste and tank-fill protection. A design aid, not a substitute for the plumbing code adopted by your AHJ.

Formula or tableTable 608.16.1: opening <= 1/2 in -> 1 in (1-1/2 in close to a wall); <= 3/4 -> 1-1/2 (2-1/2); <= 1 -> 2 (3); over 1 in -> 2x (3x) the opening; required = near_wall ? air_gap_wall : air_gap; passes = measured >= required.

Source and editionIPC 2027 §608.16.1 and Table 608.16.1 (identical in 2021) (air gaps; 608.15.1 in the 2018 numbering) and ASME A112.1.2 (Air Gaps in Plumbing Systems) by name.

Free accessFree read-only access at codes.iccsafe.org.

What governsEstimate. AHJ and licensed plumber / gas fitter govern. Verify against the IPC / IFGC edition adopted in your jurisdiction.

API field namesopening_in, near_wall, measured_in, air_gap_in, air_gap_wall_in, required_in