Economizer Enthalpy Changeover

Differential-enthalpy: enable free cooling when outdoor enthalpy < return (accounts for humidity); fixed-dry-bulb.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Enable below a setpoint. OA 24 vs RA 28 Btu/lb -> enable (4 margin); a humid OA 32 vs 28 locks out even if cool; fixed 70 F vs 65 F setpoint locks out. The ASHRAE 90.1 high-limit governs.

differential enthalpy: enable if h_outdoor < h_return; fixed dry-bulb: enable if t_outdoor < setpoint; margin = the difference to the limit.

The air-side economizer high-limit (changeover) control, differential enthalpy and fixed dry-bulb, from ASHRAE 90.1 6.5.1.1.3, by name.

The differential-enthalpy and fixed-dry-bulb high-limit logic is the published ASHRAE 90.1 economizer control requirement.

Estimate. AHJ and licensed professional govern.

Field names used by the API: mode, h_outdoor, h_return, t_outdoor_f, setpoint_f, margin