Economizer Enthalpy Changeover

Differential-enthalpy: enable free cooling when outdoor enthalpy < return (accounts for humidity); fixed-dry-bulb: enable below a setpoint. OA 24 vs RA 28 Btu/lb -> enable (4 margin); a humid OA 32 vs 28 locks out even if cool; fixed 70 F vs 65 F setpoint locks out. The ASHRAE 90.1 high-limit governs.

Run the calculator

Formula and source

differential enthalpy: enable if h_outdoor < h_return; fixed dry-bulb: enable if t_outdoor < setpoint; margin = the difference to the limit.

The air-side economizer high-limit (changeover) control, differential enthalpy and fixed dry-bulb, from ASHRAE 90.1 6.5.1.1.3, by name.

Audience

This tile is built for hvac and the adjacent professions in the HVAC group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.