Economizer Enthalpy Changeover
Differential-enthalpy: enable free cooling when outdoor enthalpy < return (accounts for humidity); fixed-dry-bulb.
Example
You enter
- Changeover type differential_enthalpy
- Outdoor-air enthalpy (Btu/lb) 24
- Return-air enthalpy (Btu/lb) 28
- Outdoor dry-bulb (°F) 70
- Fixed high-limit setpoint (°F) 65
You get
- Margin to changeover 4
No published worked example is on file for this calculation. It is checked against a hand-worked derivation of its method and an independent reference test.
Details, formula, and sources
ScopeEnable below a setpoint. OA 24 vs RA 28 Btu/lb -> enable (4 margin); a humid OA 32 vs 28 locks out even if cool; fixed 70 F vs 65 F setpoint locks out. The 90.1-2013+ combined mode also locks out a dry 80 F day whose enthalpy is below the return (75 F limit). The ASHRAE 90.1 high-limit governs.
Formula or tabledifferential enthalpy: enable unless h_outdoor > h_return; fixed dry-bulb: enable unless t_outdoor > setpoint; differential enthalpy + fixed dry-bulb (90.1-2013+): enable unless h_outdoor > h_return or t_outdoor > the entered fixed dry-bulb limit (75 F under 90.1-2013+ Table 6.5.1.1.3); margin = the difference to the binding limit.
Source and editionThe air-side economizer high-limit (changeover) control, differential enthalpy and fixed dry-bulb, from ASHRAE 90.1 6.5.1.1.3, by name.
Free accessThe differential-enthalpy and fixed-dry-bulb high-limit logic is the published ASHRAE 90.1 economizer control requirement.
What governsEstimate. AHJ and licensed professional govern.
API field namesmode, h_outdoor, h_return, t_outdoor_f, setpoint_f, margin
- Differential enthalpy enable unless h_outdoor > h_return (accounts for latent load)ASHRAE 90.1 6.5.1.1.3
- Fixed dry-bulb enable below a dry-bulb setpoint (climate-zone dependent)ASHRAE 90.1 6.5.1.1.3
- Combined (90.1-2013+) differential enthalpy with fixed dry-bulb: shut off if hOA > hRA or TOA > 75 F (all zones); plain differential enthalpy left the prescriptive table in 2013Trane Engineers Newsletter 44-2 (2015), ASHRAE 90.1-2013 Table 6.5.1.1.3
- Decision only does not model reset, minimum position, or free-cooling energyscope of this tile