ERV Total Enthalpy Recovery

Q = 4.5 x CFM x effectiveness x (h_oa - h_ra), supply enthalpy = h_oa - eff x (h_oa - h_ra). 1000 CFM, 0.75, 38 -> 28 Btu/lb -> 33,750 Btu/hr recovered, 30.5 Btu/lb supply; a winter 12 vs 28 Btu/lb recovers -54,000 Btu/hr (heating). Feed enthalpies from moist-air-enthalpy. The ERV's rated effectiveness governs.

Run the calculator

Formula and source

Q = 4.5 x CFM x effectiveness x (h_outdoor - h_return); h_supply = h_outdoor - effectiveness x (h_outdoor - h_return).

The energy-recovery-ventilator total (enthalpy) recovery relation (ASHRAE Handbook - Fundamentals / AHRI 1060 effectiveness), by name.

Audience

This tile is built for hvac and the adjacent professions in the HVAC group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.